Low Voltage Withdrawable Switchgear
MNS series Low voltage withdrawable type switchgear is used for conversion,distribution and control ofelectrical energy of power distribution equipment of AC 50~60Hz,400V.
MNS series Low voltage withdrawable type switchgear is used for conversion,distribution and control ofelectrical energy of power distribution equipment of AC 50~60Hz,400V.
Main Technical Parameters
Name | Parameter | |
Rated frequency(Hz) | 50/60Hz | |
Rated voltage(v) | 380-660v | |
Rated insulation voltage(v) | 660-1000v | |
Rated current(A) | horizontal busbar | 4000A |
vertical busbar | 2000,1000A | |
Rated short time withstand current(A) |
horizontal busbar | 50/80KA |
vertical busbar | 50KA | |
Rated peak withstand current(A) | horizontal busbar | 105/176kA |
vertical busbar | 105kA | |
Rated impulse withstand voltage | 8Kv | |
Auxiliary circuit rated voltage | AC380v,220v/DC220v | |
Maximum incoming and outgoing circuit breaker | 4000A | |
IP level | IP30,IP40,IP54 | |
Operate module | Local,Remote,Auto |
General Description
MNS series Low voltage withdrawable type switchgear is used for conversion,distribution and control ofelectrical energy of power distribution equipment of AC 50~60Hz,400V. It uses standard module design,and it can respectively form standard units such as protection,operation,conversion control,regulation,determination and indication.Over 200 types of assembly parts can form frame structures of differentschemes,andform fixed separationor drawer units.
Service conditions:
1.Installationsite:Indoor.
2.Altitude:No more than 2000m.
3.Earthquake intensity:No morethan 8 degrees
4.Ambient temperature:No more than+40 ℃ and no less than -15 ℃.Average temperature is no morethan+35℃ within 24 hours.
5.Relativehumidity:the average daily value is no morethan 95%,theaverage monthlyvalue is no morethan90%.
6.Installation locations:withoutfire,explosion danger,serious pollution,chemicalcorrosion andviolent vibration.